54 en | Configure the system PRAESENSA
2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Item Value Description
IMPORTANT: Mains and battery supervision
enabled or disabled does not influence the
impedance measurement.
Amplifier 48V power
supply (1,2,3)
Enable (default) /
Disable
IMPORTANT: Disable will stop supplying
48Vdc power supply to the amplifier and does
not indicate and report DC power supply
output failure of the connected amplifier 1, 2
and/or 3).
Enable: 48Vdc faults and/or power loss will be
indicated by the Mps front/rear panel
indicator(s) (see indicator tables at the end of
this section),
Diagnose, page 105
and
Optional:
Using the Logging Viewer, page 125
.
Amplifier lifeline audio
supervision (1,2,3)
Enable (default) /
Disable
Enable: lifeline analog audio, power supply
and/or data signal loss will be indicated by the
Mps front/rear panel indicator(s) (see indicator
tables at the end of this section),
Diagnose,
page 105
and
Optional: Using the Logging
Viewer, page 125
.
Disable: results in a system that does not
indicate and report amplifier (1, 2 and/or 3)
(analog) lifeline failures.
Submit Button Click the Submit button to store the settings.
Notice that you always have to Save the
configuration. See
Save configuration, page
102
.
Control inputs
Control inputs can be used to receive signals from third party equipment that must trigger
actions in the PRAESENSA network.
Control inputs can be configured to act on contact make or on contact break. It is also
possible to supervise the connected cables for short‑circuits and open connections. Whether a
control input is actually supervised or not is defined here in the configuration.
– Multiple calls can be started or stopped from a single control input or call station
extension button.
– This applies to Make announcement control inputs/buttons, Start phased
announcement control inputs/buttons and Stop phased announcement control
inputs/buttons. And:
– Up to five announcements can be started/stopped by a single action, e.g. an
evacuation message on one floor and alert messages on lower and higher floors. See
Actions (1-5) in the following table.
– The sub‑calls can have different priorities and zones /zone groups, but have the same
activation behavior.
For connection options, see the PRAESENSA installation manual. For an actions type overview,
see
Action definitions, page 84
.