PRAESENSA Configure the system | en 57
Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20
Item Value Description
Switch output Selection Selected on default. The control output is activated
by a Switch control output control input and/or call
station extension button.
Zone activity Selection The control output is activated when there is an active
announcement in the associated zone activated by a
control input and/or call station button.
Fault alarm buzzer Selection The control output activates a fault alarm buzzer (e.g.
a connected buzzer) each time a fault is detected in
the system. It can only be deactivated by
acknowledging all faults using a control input and/or
call station button.
Notice: Fault: relay contact open. No fault: relay
contact closed.
Fault alarm
indicator
Selection The control output activates a visual fault indicator
(e.g. a LED/lamp) each time a fault is detected in the
system. It can only be deactivated by resetting all
faults using a control input and/or call station button.
Notice: Fault: relay contact open. No fault: relay
contact closed.
Emergency alarm
buzzer
Selection The control output activates an emergency alarm
buzzer (e.g. a connected buzzer) each time a call with
priority 223 or higher is started (i.e. an emergency
announcement). It can only be deactivated by
acknowledging the emergency state using a control
input and/or call station button.
Notice: Fault: relay contact open. No fault: relay
contact closed.
Emergency alarm
indicator
Selection The control output activates a visual emergency
indicator (e.g. a LED/lamp) each time an
announcement with priority 223 or higher is started
(i.e. an emergency announcement). It can only be
deactivated by resetting the emergency state using a
control input and/or call station button.
Notice: Fault: relay contact open. No fault: relay
contact closed.
System fault
indicator
Selection The control output activates a visual fault indicator
(e.g. a LED/lamp); each time a system fault is
detected in the system. System faults are a special
category of faults, a subset of all possible faults. See
also
Event messages, page 134
Notice: Fault: relay contact open. No fault: relay
contact closed.
Submit Button Click the Submit button to store the settings. Notice
that you always have to Save the configuration. See
Save configuration, page 102