Camus ProtoNode Start-up Guide
Page 11 of 87
3.3 Configuring Device Communications
3.3.1 Confirm the Device and ProtoNode COM Settings Match
• Any connected serial device MUST have the same baud rate, data bits, stop bits, and
parity settings as the ProtoNode.
• Figure 4 specifies the device serial port settings required to communicate with the ProtoNode.
Port Setting Sola Valiant DynaFLO
Figure 4: COM Settings
3.3.2 Set Node-ID for Any Device Attached to the ProtoNode
• Set Node-ID for any device attached to ProtoNode. The Node-ID needs to be uniquely assigned
between 1 and 255.
• Document the Node-ID that is assigned to any device. The Node-ID assigned is used for deriving
the Device Instance for BACnet/IP and BACnet MS/TP. (Section 3.5.2)
NOTE: The Metasys N2 or Modbus TCP/IP field protocol Node-ID is automatically set to be the
same value as the Node-ID of the device.