Camus ProtoNode Startup
G id
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web:
www.protocessor.com
Tel: (408) 964-4444 Fax: (408) 964-4425 email: support@protocessor.com
Camus ProtoNode Startup
G id
Page 57 of 87
Appendix C. Vendor InformationCamus
NOTE: All Modbus TCP/IP registers are the same as the Modbus RTU registers for the serial device. The Modbus TCP/IP node address of the device is also
the same as the Modbus RTU node address.
Sola Modbus RTU Mappings to BACnet, Metasys N2, Modbus TCP/IP & LonWorks
Point Name
R/W
Modbus
Address
(hex)
Modbus
Register
(dec)
BACnet
Object
Type
BACnet
Object
ID / N2
Point
Address
N2
Data
Type
Lon Name
Lon SNVT
Note
Demand source
R
0006
0006
AI
2
AI
nvoXDemandSource
SNVT_count_f
0 = Unknown
1 = No source demand
2 = CH
3 = DHW
4 = Lead Lag slave 5
= Lead lag master
6 = CH frost protection
7 = DHW frost protection
8 = No demand due to burner
switch turned off
9 = DHW storage
10 = Reserved
11 = Warm weather shutdown
Outlet sensor
R
0007
0007
AI
3
AI
nvoXOutletSensor
SNVT_temp_p
-40 130
o
C (0.1
o
C precision)
1
Firing rate
R
0008
0008
AI
4
AI
nvoXFiringRate
SNVT_count_f
Actual Fire Rate (%
2
or RPM
3
)
Fan speed
R
0009
0009
AI
5
AI
nvoXFanSpeed
SNVT_count_f
RPM
Used on all DynaMax, Dynaforce® 300
1000, Advantus™ 500 - 600
Flame signal
R
0010
0010
AI
6
AI
nvoXFlameSignal
SNVT_count_f
0.01V (0.00 50.00V)
Inlet sensor
R
000B
0011
AI
7
AI
nvoXInletSensor
SNVT_temp_p
40 200
o
F
1
DHW sensor
R
000C
0012
AI
8
AI
nvoXDHWSensor
SNVT_temp_p
40 200
o
F
1
S5 sensor
R
000D
0013
AI
9
AI
nvoXS5Sensor
SNVT_temp_p
40 200
o
F
1
Stack sensor
R
000E
0014
AI
10
AI
nvoXStackSensor
SNVT_temp_p
40 200
o
F
1
4 - 20 mA remote ctl
input
R
000F
0015
AI
11
AI
nvoX420mARmCtlIn
SNVT_count_f
4-20mA (0.1mA precision)
Active CH setpoint
R
0010
0016
AI
12
AI
nvoXActiveCHSP
SNVT_temp_p
40 200
o
F
1
Active DHW setpoint
R
0011
0017
AI
13
AI
nvoXActiveDHWSP
SNVT_temp_p
40 200
o
F
1