Appendix A. Troubleshooting
Lost or Incorrect IP Address
Ensure that FieldServer Toolbox is loaded onto the local PC. Otherwise, download the
FieldServer-Toolbox.zip via the Sierra Monitor website’s Software Downloads
.
Extract the executable file and complete the installation.
Connect a standard Cat-5 Ethernet cable between the user’s PC and ProtoNode.
Double click on the FS Toolbox Utility and click Discover Now on the splash page.
Check for the IP Address of the desired gateway.
If correcting the IP Address of the gateway: click the settings icon on the same row as the
gateway, then click Network Settings, change the IP Address and click Update IP Settings to save.
Ethernet Port
Figure 40: Ethernet Port Location