4.6.2 End of Line Termination Switch for the RS-485 Device Network
On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each end.
The ProtoNode has an end of line (EOL) blue jumper. The default setting for this blue EOL switch
is OFF with the jumper straddling the pins closest to the inside of the board of the ProtoNode.
o On short cabling runs the EOL switch does not to need to be turned ON
If the ProtoNode is placed at one of the ends of the trunk, set the blue EOL jumper to the ON
position straddling the pins closest to the outside of the board of the ProtoNode.
Always leave the single red jumper in the A position (default factory setting).
RS-485 EOL
Switch
(off)
Leave in Position A
Figure 12: RS-485 End-Of-Line Termination Switch on the ProtoNode N34 (Left) and
ProtoNode N35 (Right)