ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com
Tel: (408) 964-4444 Fax: (408) 964-4425 email: support@protocessor.com
0: Initializing
1: Reset
2: Standby
3: Pre-purge 0
4: Pre-purge 1
5: Pre-ignit
6: Ignit
7: Flame proving
8: Burn
9: Post-burn
10: Post-purge 0
11: Post-purge 1
12: Error check
13: Alarm
14: Burner boot
BM_Unit_11_Error R AI 123 AI 40002 nvoU11Err_XXX SNVT_count_f
Please check the Valiant manual for more
detailed information on each state.
0 99 = Locking errors
100 199 = Blocking errors
200 255 = Warnings
255 = No error / warning
BM_Unit_11_CalcSetpoint
R
AI
124
AI
40003
nvoU11ClSP_XXX
SNVT_temp_p
BM_Unit_11_PowerLevel
R
AI
125
AI
40004
nvoU11PwLv_XXX
SNVT_count_f
BM_Unit_11_GenPumpStatus
R
AI
126
AI
40007
nvoU11GnPmSt_XXX
SNVT_count_f
BM_Unit_11_ChFlowRate
R
AI
127
AI
40010
nvoU11ChFlRt_XXX
SNVT_count_f
BM_Unit_11_ActualFanSpeed
R
AI
128
AI
40012
nvoU11AcFnSp_XXX
SNVT_count_f
BM_Unit_11_SupplySensor
R
AI
129
AI
40031
nvoU11SupSen_XXX
SNVT_temp_p
BM_Unit_11_ReturnSensor
R
AI
130
AI
40033
nvoU11RetSen_XXX
SNVT_temp_p
BM_Unit_11_FlueSensor
R
AI
131
AI
40036
nvoU11FlSen_XXX
SNVT_temp_p
BM_Unit_11_TotBurnHours
R
AI
132
AI
40053
nvoU11ToBnHr_XXX
SNVT_time_hour
BM_Unit_12_CurrentState
R
AI
133
AI
40101
nvoU12CrSt_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_12_Error
R
AI
134
AI
40102
nvoU12Err_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_12_CalcSetpoint
R
AI
135
AI
40103
nvoU12ClSP_XXX
SNVT_temp_p
In Cascade mode only
BM_Unit_12_PowerLevel
R
AI
136
AI
40104
nvoU12PwLv_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_12_GenPumpStatus
R
AI
137
AI
40107
nvoU12GnPmSt_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_12_ChFlowRate
R
AI
138
AI
40110
nvoU12ChFlRt_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_12_ActualFanSpeed
R
AI
139
AI
40112
nvoU12AcFnSp_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_12_SupplySensor
R
AI
140
AI
40131
nvoU12SupSen_XXX
SNVT_temp_p
In Cascade mode only
BM_Unit_12_ReturnSensor
R
AI
141
AI
40133
nvoU12RetSen_XXX
SNVT_temp_p
In Cascade mode only
BM_Unit_12_FlueSensor
R
AI
142
AI
40136
nvoU12FlSen_XXX
SNVT_temp_p
In Cascade mode only
BM_Unit_12_TotBurnHours
R
AI
143
AI
40153
nvoU12ToBnHr_XXX
SNVT_time_hour
In Cascade mode only
BM_Unit_13_CurrentState
R
AI
144
AI
40201
nvoU13CrSt_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_13_Error
R
AI
145
AI
40202
nvoU13Err_XXX
SNVT_count_f
In Cascade mode only
BM_Unit_13_CalcSetpoint
R
AI
146
AI
40203
nvoU13ClSP_XXX
SNVT_temp_p
In Cascade mode only
BM_Unit_13_PowerLevel
R
AI
147
AI
40204
nvoU13PwLv_XXX
SNVT_count_f
In Cascade mode only

Table of Contents