Appendix C:  RTU Open Points/Properties on the Equipment Touch   
 
 
 
 
RTU Open v3    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  100 
 
Setpoints - Equipment Touch 
 
 
 
 
 
 
 
 – Green 
The heating setpoint the controller maintains while in occupied mode.
 
D: 
R: 
70°F (21.1°C) 
40 to 90°F 
(4.4 to 32.2°C) 
 – Green 
The cooling setpoint the controller maintains while in occupied mode.
 
D: 
R: 
76°F (24.4°C) 
 55 to 99°F 
(12.7 to 37.2°C) 
 – Gray 
The heating setpoint the controller maintains while in unoccupied mode.
 
D: 
R: 
55°F (12.7°C)  
40 to 90°F 
(4.4 to 32.2°C) 
 – Gray 
The cooling setpoint the controller maintains while in unoccupied mode.
 
D: 
R: 
90°F (32.2°C) 
45 to 99°F 
(7.2 to 37.2°C) 
 
 – The method used to change from unoccupied to occupied setpoint. 
Options: 
– Unit will not change to occupied setpoint until the scheduled time or the unit goes into an 
occupied mode. Setpoints do not ramp, but change immediately from unoccupied to occupied 
values. 
– Unit changes to occupied setpoints at a variable time prior to the occupied 
time, which is calculated by the current difference between space temperature and the 
appropriate heating or cooling setpoint. At that time, the setpoints do not ramp, but change 
immediately from unoccupied to occupied values. 
– Unit gradually changes to occupied setpoints by adjusting the 
unoccupied setpoints over a specified period of time to achieve the occupied setpoint by the time 
scheduled occupancy begins.
 
D: 
 
R: 
Temperature 
Compensated 
None 
Temperature 
Compensated 
Learning 
Adaptive 
Heat Start K factor (min/deg)
 – If 
 is 
, this is the time in 
minutes per degree that the equipment starts before the occupied period when the space 
temperature is below the occupied heating setpoint (including any setpoint offset). 
 
D: 
R: 
15.00 
0 to 99 
Cool Start K factor (min/deg)
 – If 
 is 
, this is the time in 
minutes per degree that the equipment starts before the occupied period when the space 
temperature is above the occupied cooling setpoint (including any setpoint offset). 
 
D: 
R: 
 
15.00 
0 to 99