Sequence of Operation   
 
 
 
 
RTU Open v3    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  46 
 
•  Heat mode is not active and the 5-minute time guard between modes has expired 
•  Economizer is unavailable, or if the Economizer is active, mechanical cooling is available if the economizer is 
open > 90% for at least 7.5 minutes, the SAT and OAT > [
 + 5 °F (2.7 °)] and SPT > 
[
Effective Cooling Setpoint
 + 0.5 °F (.27 °C)]. 
 
The cooling relays are controlled by the Cooling Control PID Loop and Cooling Capacity algorithm. They calculate 
the desired number of stages needed to satisfy the space by comparing the 
 to the: 
• 
Effective Occupied Cooling Setpoint 
when occupied 
• 
Effective Unoccupied Cooling Setpoint
 when unoccupied 
 
When the cooling algorithm preconditions have been met, the compressors are energized in stages, as applicable. 
Anti-recycle timers are employed to protect the equipment from short-cycling. There are fixed 3 minute minimum 
on-times, and 5 minute off-times for each compressor output. 
During compressor operation, the RTU Open may reduce the number of active stages if the rooftop supply air 
temperature falls below the 
Minimum Cooling SAT Setpoint
. A compressor staged off in this fashion may be 
started again after the normal time-guard period has expired, if the 
 has increased above 
the 
Minimum Cooling SAT Setpoint
. 
Compressor Service Alarm Timer
 functions are available (1 for each stage of compression). This function tracks 
the number of compressor run hours and generates an alarm when the accumulated runtime exceeds the 
threshold set by the adjustable compressor service alarm timers. 
 
 
 
The RTU Open provides an analog economizer output for rooftop units with economizer dampers. Economizer 
dampers may be used to provide indoor air quality control and free cooling when outside air conditions are 
suitable. 
The following conditions must be true for economizer operation: 
•  The 
 is less than the 
 and less than the 
Economizer High OAT 
Lockout Temp
 setpoint 
•  The indoor fan is on 
•  The unit has a valid 
 input 
•  The unit has a valid 
 input 
 
If the RTU Open is configured for VFD or 2-speed fan, the economizer minimum position is adjusted to provide a 
constant amount of outdoor air. If the fan is on high speed or is configured for single-speed fan, the economizer 
minimum position will be set to the 
Vent Dmpr Pos / DCV Min Pos
 setpoint. If it is configured for VFD or 2-speed 
fan, and the fan is on low speed, the economizer minimum position will be set to the 
. 
If all preceding conditions are true, the economizer PID loop modulates the damper between the minimum 
position and 100% open. 
The economizer will modulate to maintain the configured
 limit when the unit is in an 
economizer only mode and will modulate closed only when the SAT drops below the 
 
 limit - 
5
°F (-2.8 °C) when mechanical cooling is also operating.