Start-up
   
 
 
 
RTU Open v3    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  41 
 
Use one of the following interfaces to start up, access information, read sensor values, and test the controller. 
 
 
 
application - 
Runs on a laptop that connects to controller's Local Access port 
1
 
Temporary interface 
 device - 
Connects to controller's Rnet port
 2
 
Temporary or permanent 
interface  
 application 
Available for BACnet systems only 
 
Permanent interface 
 device  
Available only for BACnet MS/TP systems.  
Wire to a BACnet MS/TP network connector and a 24 Vac power supply 
3
 
Temporary or permanent 
interface  
1
 Requires a USB Link (Part #USB-L). 
2
  See the Equipment Touch Installation and Setup Guide for detailed instructions. 
3
  See the System Touch Installation and Setup Guide for detailed instructions. 
 
 If multiple controllers share power but polarity was not maintained when they were wired, the 
difference between the controller's ground and the computer's AC power ground could damage the USB Link and 
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB 
Link. Purchase a USB isolator online from a third-party manufacturer. 
 
 
 
 
> 
> 
> 
> 
 
 
 
 can be used to verify proper operation of compressors, heating stages, indoor fan, power exhaust 
fans, economizer, and dehumidification. It is highly recommended to use 
 at initial system start-up 
and during troubleshooting. See Appendix A: Points/Properties (page 
62) for more information. 
To activate 
, the unit must be shut down first. In Field Assistant, or the i-Vu® interface, you can verify 
on the 
 > 
 tab that the BBV
 shows 
.  
 can be turned on or off from a Field Assistant or i-Vu® interface in 
>
 
(page 
80), but not from an Equipment Touch. Select 
 of 
to turn on and 
 to turn off.  
 
 differs from normal operation as follows:  
•  Outdoor air temperature limits for cooling circuits, economizer, and heating are ignored.  
•  Normal compressor time guards and other staging delays are ignored.  
•  Alarm statuses (except 
 and 
) are ignored, but all alarms and alerts are still broadcast on the 
network, if applicable.