Installing the RTU Open   
 
 
 
 
RTU Open v3    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  38 
 
To wire a status switch to the controller 
 
 
•  Binary inputs 3, 5, 8, and 9 are configurable and may be used for 
, 
, 
 or 
, if they have not already been used for their default functions. 
•  Follow device manufacturer's installation and operating instructions. 
 
 
 
Wiring a compressor safety 
This is typically provided by the manufacturer with the rooftop equipment. A compressor safety status may be 
monitored if available.   
 
 
 
Wiring specifications 
 
Cable from sensor to controller:  If <100 ft (30.5 meters)        22 AWG, unshielded 
If >100 ft (30.5 meters) 22 AWG, shielded 
Maximum length:  500 feet (152 meters)