Installing the RTU Open
   
 
 
 
RTU Open v3    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  35 
 
Wiring an enthalpy switch 
Outdoor Air - Part #33CSENTHSW 
Return air - Part #33CSENTSEN 
 
The 33CSENTHSW is an outdoor air enthalpy switch/receiver. This control determines the suitability of the outdoor 
air as a cooling source, based on the heat content of the air. Differential enthalpy control requires installing a 
33CSENTSEN enthalpy sensor in the rooftop unit's return air duct. 
 
 
 
Wiring specifications 
 
Cable from sensor to controller:  If <100 ft (30.5 meters)        22 AWG, unshielded 
If >100 ft (30.5 meters)        22 AWG, shielded 
Maximum length:  500 feet (152 meters) 
 
 
 
To wire an enthalpy switch (outdoor air) to the controller 
An enthalpy switch is typically mounted in the outdoor air inlet. 
 