EasyManua.ls Logo

Carrier RTU Open v3 - Device Address Binding

Carrier RTU Open v3
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B: Single Point Linkage and Device Address Binding
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
92
Device Address Binding
Device Address Binding
(DAB) allows the controller to receive data from other Open controllers when they are
connected by a network. The controller receives data from other Open or BACnet controllers when they are
installed as part of an i-Vu® Control System. The data transfer takes the form of DAB, which you must configure.
Currently, the controller implements DAB for the following variables:
System Outdoor Air Temperature
System Occupancy
System Leaving Load Water Temp
System Control Setpoint
System Cool Demand Level
System Space RH
You can implement DAB on network points with an undefined BACnet address, displayed in Field Assistant and the
i-Vu® interface on the
Properties
page >
Network Points
tab. See example below.

Table of Contents

Other manuals for Carrier RTU Open v3

Related product manuals