Appendix C:  RTU Open Points/Properties on the Equipment Touch
   
 
 
 
RTU Open v3    CARRIER CORPORATION ©2019  
Installation and Start-up Guide    All rights reserved 
  95 
 
 
 
 
 
 
 – The type of equipment that the RTU Open is controlling. 
Options: 
 – Standard rooftop air handling unit. 
™
– A special factory-supplied 3-stage cooling unit 
 – Heat Pump application, uses reversing valve output to control heating 
and cooling. 
 – Carrier Heat Pump application only. 
D: 
R: 
Heat/Cool 
Heat/Cool 
LC WeatherExpert™ 
HP O/B Ctrl 
HP Y1/W1 Ctrl 
 – The type of heating used by the unit. 
 
D: 
R: 
Electric 
Electric/Gas 
 – The number heat stages.  D: 
R: 
2 
1 / 2  /0 (no heating) 
 – The number of mechanical cooling stages. 
 
D: 
R: 
One Stage 
One Stage 
Two Stages 
 – The type of fan control used on this unit. 
Automatically set to 
 if 
 is set to 
. 
D: 
R: 
Single Speed 
Single Speed 
Two Speed 
Variable Speed 
 – Set to 
to enable economizer control for units equipped with an 
economizer damper.
 
D: 
R: 
No 
No/Yes 
Economizer High OAT Lockout
 
– The outdoor air temperature above which 
economizer cooling is inhibited.
 
D: 
R: 
75°F (23.9°C) 
55 to 80°F 
(12.7 to 26.6°C) 
Vent Dmpr Pos / DCV Min Pos
 – The minimum outdoor air damper position maintained 
during occupied periods.
 
D: 
R: 
20% Open 
0 to 100% 
 – The minimum outdoor air damper position maintained 
during an unoccupied purge cycle when the Pre-Occ Purge mode is active.
 
D: 
R: 
40% Open 
0 to 100% Open 
 – The minimum outdoor air damper position maintained during 
occupied periods when the fan is running at low speed (if configured for 2-speed fan 
control) or the minimum VFD speed (if configured for variable speed fan control).
 
D: 
R: 
33% Open 
0 to 100% Open 
 – Enables dehumidification control if an RH sensor or humidistat is 
available and the unit has the Humidi-MiZer™ dehumidification option installed.
 
D: 
R: 
Disable 
Disable/Enable 
 – Enables demand controlled ventilation (DCV) if valid CO
2
 sensor value is 
available and the unit has an economizer installed.  
D: 
R: 
Disable 
Disable/Enable