not change with units, _Fand_C. This can allow one setting to push” the other to
maintain this difference. When the correct deadband is set, touch SAVE.
S Deadband: Adjustable from 0 to 6_
d Default = 2_
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch SAVE.
S Outdoor temperature: Adjustable from --5 to 5_F(--3to3_C)
d Default = 0_F
S Humidity: Adjustable from --10 10%
d Default = 0%
6.3.1.4. Reset factory defaults
This option allows the installer to reset certain factory parameters. After the
selections are made, touch SAVE.
S Program Schedule: Reset back to pre--programmed time and temperature.
S User Settings: Reset user settings back to pre--programmed values.
S Install Settings: Reset installation settings back to pre--programmed values.
S Last 10 Faults: Reset the last 10 system faults under the Service menu.
6.3.1.5. Scheduling Enable
This option lets the installer allow programming features. After the selection is
made, touch SAVE.
S Scheduling: On or Off
d Default = On