44
heating capacity. Reducing this value will reduce the heating capacity of the heat
pump. After the selection is made, touch SAVE.
S AC Heat Pump Max RPM: Adjustable from 4500 – 7000
d Default = 7000 RPM
6.3.4.7. Defrost Fan Delay
Turns on the outdoor unit fan at the end of a defrost cycle for approximately 12
seconds. This helps to reduce any nuisance refrigerant noise caused by the
switching reversing valve. This setup is only available on communicating heat
pumps. After the selection is made, touch SAVE.
S Defrost Fan Delay: Yes or No
d Default = No
6.3.4.8. Brownout Disable
This option turns off the high voltage brownout detection function in the outdoor
unit control. After the selection is made, touch SAVE.
S Brownout Disable: On or Off
d Default = Off
6.3.4.9 Low Air Multiplier
Adjusts the airflow speed on non--communicating two--stage units. Choose 0.65 for
units with a Bristol compressor, choose 0.80 (default) for units with a Copeland
scroll compressor.
6.3.4.10. Energy Efficiency
This option is used to input the published ratings of the installed air conditioner or
heat pump as part of the energy tracking calculation. After the ratings are entered,
touch SAVE.