EasyManua.ls Logo

CET PMC-53A - 4.1.6 RTD Input; 4.2 Power and Energy; 4.2.1 Basic Measurements

CET PMC-53A
103 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CET Electric Technology
38
There are 4 setup parameters:
Type: Select between 0-20mA or 4-20mA output.
AO Zero: Defines the zero scale value of the parameter when the Analog Output is 0 or 4 mA
according to the AO Type. The value ranges between -999,999 to +999,999.
AO Full: Defines the full scale value of the parameter when the Analog Output is 20 mA. The
value ranges between -999,999 and +999,999.
Key: Defines the parameter to which the Analog Output is proportional. The Analog Output
Parameters are listed in Table 3-13.
For example, an AO of 4-20mA is required to be proportional to Phase A current. The maximum value
of phase A current is 2000A, and the minimum value is 500A. As such, the Type parameter should be
programmed as 4-20mA. The Key parameter should be programmed with Ia (Phase A Current). The AO
FULL parameter should be programmed with the value 2000. The AO ZERO parameter should be
programmed with the value 500. Therefore, when Phase A Current is 500A or below, The AO output is
4mA. When Phase A Current is 2000A, the AO output is 20mA. When Phase A Current is 1250A, the AO
is (1250A-500A) x (20mA-4mA) / (2000A-500A) + 4mA = 12.00 (mA).
4.1.6 RTD Input
The PMC-53A optionally provides two RTD Inputs for temperature measurements. The PT100 sensors
are optional and not included. The 2-wire outputs of the PT100 sensor are connected to the RTD Input
of the PMC-53A if so equipped. The PMC-53A can provide accurate temperature monitoring with the
optional RTD inputs for measuring the temperature of the Neutral Conductor, Transformer or other
equipment. There is a RTD Compensation register for each channel which can be used to compensate
the measurement accuracy, and the compensation can be set according to formula:
RTD Compensation = 0.29xL where L ≤ 8 is the PT100 sensor’s cable length in m
4.2 Power and Energy
4.2.1 Basic Measurements
The PMC-53A provides the following basic measurements which are available through the Front Panel
or communications.
Parameter
Phase A
Phase B
Phase C
Total
Average
Uln
-
Ull
-
Current
-
Neutral Current
-
-
-
In (Calculated)
I4 (Optional)
Residual
Current~
-
-
-
Ir~
-
kW
-
kvar
-
kVA
-
Power Factor
-
Frequency
-
-
-
-
U Fundamental*
I Fundamental*
U Sequence*
U1 (Positive Sequence)
U2 (Negative Sequence)
U0 (Zero Sequence)
I Sequence*
I1 (Positive Sequence)
I2 (Negative Sequence)
I0 (Zero Sequence)
* Available in Firmware V1.00.03 or later.
~ Available in Firmware V1.00.06 or later.
Table 4-2 Basic Measurements

Table of Contents

Other manuals for CET PMC-53A

Related product manuals