3.3.3 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Label
Description
Range
Default
Menu
1
st
2
nd
3
rd
Password
Enter Password
0000 to 9999
0000
Basic
Wiring Mode
Meters Wiring Connection
DEMO/
1P2W L-N/1P2W L-L/
1P3W/3P3W/3P4W
3P4W
PT Primary
PT Primary Ratio
1 to 1000000V
100V
PT Secondary
PT Secondary Ratio
1 to 690V
100V
CT Primary
CT Primary Ratio
1 to 30000A
5A
CT Secondary
CT Secondary Ratio
1 to 5A
5A
I4 Primary~
I4 Primary Ratio
1 to 30000A
5A
I4 Secondary~
I4 Secondary Ratio
1 to 5A
5A
PF Convention
PF Convention
IEC/IEEE/-IEEE
IEC
kVA Calc.
kVA Calculation Method
Vector/Scalar
Vector
I1 Polarity
I1 Polarity
Normal/Reversed
Normal
I2 Polarity
I2 Polarity
I3 Polarity
I3 Polarity
THD Calc.
Select between
% of Fundamental or
% of RMS
THDf/THDr
THDf
DMD Period
Demand Interval
1 to 60 min
15
No. of Windows
Number of Sliding Windows
1 to 15
1
Predicted Resp.
Predicted Response
70 to 99
70
EN Pulse CNST
Pulse Constant
1000/3200
1000
LED EN Pulse
Enable kWh/kvarh Energy
Pulsing
Disabled/kWh/kvarh
kWh
EN Period*
Interval Energy period
5 to 60 min
60
kvarh Calc.~
kvarh Calculation Method
RMS/FUND
RMS
OT Threshold~
Current Threshold of
Device Operating Time
1 to 1000 (x0.001In)
1
Comm.
COM1
Protocol
Protocol
Modbus/BACnet*/N2*/DNP~
Modbus
Unit ID
Modbus Address
Modbus RTU/N2*: 1 to 247
BACnet/MSTP*: 1 to 127
DNP~: 0 to 65519
100
Baud Rate
Data rate in bits per second
1200/2400/4800/
9600/19200/38400
9600
Data Format
Data Format
8N2/8O1/8E1/
8N1/8O2/8E2
8E1
COM2
Protocol
Protocol
Modbus
Modbus
Unit ID
Modbus Address
1 to 247
101
Baud Rate
Data rate in bits per second
1200/2400/4800/
960019200/38400
9600
Data Format
Data Format
8N2/8O1/8E1/
8N1/8O2/8E2
8E1
Setpoint*
Group #1
Type
Setpoint Type
0=Disabled, 1=Over Setpoint
2=Under Setpoint
0
Parameter
1
Setpoint Source
See Table 3-11
None
OvLim
Over Limit
0
UnLim
Under Limit
0
ActiveDelay
Active Delay
0 to 9999s
10
InactiveDelay
Inactive Delay
0 to 9999s
10
Trigger1
2
Setpoint Trigger1
See Table 3-12
Trigger2
2
Setpoint Trigger2
See Table 3-12