Emotron VS Series Quick Start Guide
- 50 -
A0.20
Inverter rated power
0.0~1000.0kW
Model
defined
⊙
A0.21
Inverter rated voltage
60~660V
Model
defined
⊙
A0.22
Inverter rated current
0.1~1500.0A
Model
defined
⊙
A0.23
Software version
0.00~655.35
Model
defined
⊙
A0.24
Dealer password
0~99999
0
×
A0.25
Operation time
0~65535h(0: Invalid)
0h
×
Group b0: Frequency Command
b0.00
Frequency source
selection
0: Master frequency source
0
×
1: Auxiliary frequency source
2: Master +Auxiliary
3: Master - Auxiliary
4: MAX{Master, Auxiliary }
5: MIN {Master, Auxiliary }
6: AI1 ( Master + Auxiliary )
7: AI2 ( Master +Auxiliary )
b0.01
Master Frequency
Command Source
0:Master digital setting (b0.02)
0(VSX)
1(Others)
×
1: keypad potentiometer
(When using LED keypad)
2: Analog input AI1
3: Communication
4: Multi-reference
5: PLC
6: Process PID output
7: X7/HI pulse input
8: AI2
9: AI3 (VSX Only)
b0.02
Digital Setting of Master
Frequency
0.00~Fmax
50.00Hz
△
b0.03
Auxiliary Frequency
Command Source
0: Auxiliary digital setting (b0.04)
0
×
1: keypad potentiometer
2: Analog input AI1
3: Communication
4: Multi-reference
5: PLC
6: Process PID output
7: X7/HI pulse input
8: Analog input AI2
9: Analog input AI3 (VSX Only)
b0.04
Digital setting of
auxiliary frequency
0.00~Fmax
50.00Hz
△
b0.05
Range of auxiliary
frequency
0: Relative to maximum frequency
0
×
1: Relative to master frequency
b0.06
Coeff of auxiliary
frequency
0.0~150.0%
100.0%
△
b0.07
Jog frequency
0.00~Fmax
5.00Hz
△
b0.08
Maximum frequency
20.00~600.00Hz
50.00Hz
×
b0.09
Upper limit frequency
Fdown~Fmax
Lower limit frequency~maximum
frequency
50.00Hz
×
b0.10
Lower limit frequency
0.00~Fup
0.00Hz
×
b0.11
Operation when command
0: Run at lower limit frequency
0
×

Table of Contents