Connect Wiring
Review Electrical Input and Output
Refer to the CT4000 Data Sheet for electrical input and output specifications.
CAUTION: Use copper conductors only.
Do not provide GFCI protection at the panel. The CT4000 has built-in GFCI protection.
Use breakers rated at 40 A (or lower, if you are configuring the station to operate at a lower
current capacity).
In areas with frequent thunderstorms, add surge protection at the service panel for all circuits.
Use new circuit breakers only.
Ensure all power and ground connections (especially those at the breaker) are clean and tight.
Remove all oxide from all conductors and terminals before connecting wiring.