5.4.- CONNECTION AND RECLOSING TIME
In this point the action times of the device are configured in seconds:
Ton is the minimum time between the connection and disconnection of a single stage.
TREC is the maximum time between the disconnection and connection of a single stage.
TREC must be greater than ToN; ideally, it should be 5 times greater.
 
Press the   key to enter edit mode. It is identified by the   symbol and the flashing of the 
digits to be modified.
The   key increases the digit value.
The   key reduces the digit value.
The   key skips to the previous digit and the   key skips to the next digit.
Press   to validate the data; the   symbol disappears from the display.
Ton: 
   Maximum value: 999.
 Minimum value: 4.
Trec: 
   Maximum value: 999.
   Minimum value: 20.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight 
of the display flashes and the value entered is replaced with the minimum or maximum value, or with 
the last value validated. 
Press the   key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen, “5.30.- SIMULATION 
SCREEN”.
77
Instruction Manual
Computer SMART III