EasyManuals Logo

Circutor Computer SMART III 14 User Manual

Circutor Computer SMART III 14
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
5.13.- HYSTERESIS
The L (inductive) and C (capacitive) hysteresis values of the target cos φ are specified in this section.
As long as the cos φ is within this range, the device does not connect any paths, but it can disconnect
them.
The configuration of the hysteresis affects the four target cos φ specified.
Note: If the hysteresis is activated on the display screens, the symbol flashes every 5 seconds.
Press the key to enter edit mode. It is identified by the symbol and the flashing of the
digits to be modified.
The key increases the digit value or shows the next option.
The key reduces the digit value or shows the next option.
The key skips to the previous digit and the key skips to the next digit.
Press to validate the data; the symbol disappears from the display.
Maximum value: 0.10.
Minimum value: 0.00.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen, 5.30.- SIMULATION
SCREEN”.
87
Instruction Manual
Computer SMART III

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor Computer SMART III 14 and is the answer not in the manual?

Circutor Computer SMART III 14 Specifications

General IconGeneral
BrandCircutor
ModelComputer SMART III 14
CategoryController
LanguageEnglish

Related product manuals