Cleaver-Brooks CBW - F. Modulating Motor Does Not Operate

Default Icon
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER6
(7) Improper air.fuel ratio (lean fue ).
(a) Slipping linkage.
(b) Damper stuck open.
(c) Fluctuating fuel supply.
(i) Temporary obstruction in fuel
line.
(ii) Temporary drop in gas pressure.
(iii) Orifice gate valve accidentally
opened (heavy oil).
(8) Interlock device inoperative or defec-
tive.
F.
MODULATING
MOTOR
DOES
NOT
OPERATE
(1) Manual-automatic switch
in
wrong
position.
(2) Linkage loose
or
jammed.
750-150
TROUBLE
SHOOTING
(3) Motor does not drive
to
open
or
close
during pre-purge or close on burner
shut·
down.
(a) Motor defective.
(b)
Loose
electrical connection.
(c) Damper motor transformer defective.
(4) Motor does not operate on demand.
(a)
Manual:-automatic switch
in
wrong
position.
(b) Modulating control improperly set or
inoperative.
(c) Motor defective.
(d) Loose electrical connection.
(e) Damper motor transformer defective.
CHAPTER
6..S