Section 4 — CFC Commissioning
Part No. 750-263 4-13
Anti-condensation Configuration
CH anti-condensation pump
force off
Service Disabled 0498
Anti-condensation Configuration
DHW anti-condensation
enable Service Disabled 0499
Anti-condensation Configuration
DHW anti-condensation
setpoint Service 32 140 194 °F 0500
Anti-condensation Configuration
DHW anti-condensation
pump force off
Service Disabled 0501
Anti-condensation Configuration
Anti-condensation > Outlet
limit Service No 0502
Anti-condensation Configuration Anti-condensation > Delta-T Service No 0502
Anti-condensation Configuration
Anti-condensation > Stack
limit Service No 0502
Anti-condensation Configuration
Anti-condensation > Slow
start Service Yes 0502
Anti-condensation Configuration
Anti-condensation > Forced
rate Service Yes 0502
Anti-condensation Configuration
Frost protect
anticondensation enable Service No 0503
Frost Protection Configuration CH frost protection enable Service Disabled 0528
Frost Protection Configuration DHW frost protection enable Service Disabled 0529
Frost Protection Configuration
Outdoor frost protection
setpoint Service -40 32 120 °F 0530
Frost Protection Configuration LL frost protection enable Service Disabled 0532
Frost Protection Configuration LL frost protection rate Service 0 20% 100 0533
Lead Lag Configuration Lead Lag slave enable Service Disabled 0544
Lead Lag Configuration Lead Lag master enable Service Disabled 0545
Lead Lag Configuration Lead Lag CH setpoint Service 32 150 230 °F 0546
Lead Lag Configuration Lead Lag CH TOD setpoint Service 32 120 230 °F 0547
Lead Lag Configuration Lead Lag on hysteresis Service 5 °F 0549
Lead Lag Configuration Lead Lag off hysteresis Service 15 °F 0550
Lead Lag Configuration
Lead Lag hysteresis step
time Service 60 seconds 0551
Lead Lag Configuration Lead Lag P gain Service 0 10 400 0552
Lead Lag Configuration Lead Lag I gain Service 0 25 400 0553
Lead Lag Configuration Lead Lag D gain Service 0 0 400 0554
Lead Lag Configuration Lead Lag operation switch Service Yes/True/On 0555
Lead Lag Configuration Lead Lag CH demand switch Service STAT terminal 0556
Lead Lag Configuration Lead Lag CH setpoint source Service Local 0557
Lead Lag Configuration
Lead Lag modulation backup
sensor Service
Use average of all
slave outlet sensors 0559
Lead Lag Configuration
Lead Lag CH 4mA water
temperature Service 80 °F 0560
Lead Lag Configuration
Lead Lag CH 20mA water
temperature Service 180 °F 0561
Lead Lag Configuration Slave mode Service Equalize run time 0564
Lead Lag Configuration Base load rate Service 800 2000 6000 RPM 0566
Lead Lag Configuration Fan rate during off cycle Service 0 0 6000 RPM 0567
Lead Lag Configuration Slave sequence order Service 0 0568
Lead Lag Configuration Lead Lag Modbus port Service MB2 0569
Lead Lag Configuration
Lead Lag slave demand to
firing delay Service 60 300 seconds 0570
Lead Lag Configuration Base load common Service 0 45% 100 % 0572
Lead Lag Configuration Lead selection method Service
Lowest measured run
time 0574
Lead Lag Configuration Lag selection method Service
Rotate in sequence
order 0575
Lead Lag Configuration
Lead Lag add stage method
1 Service Firing rate threshold 0714
Table 4-1 CFC default parameter settings
Parameter Group Parameter Name Access*
Min.
Range Default Setting
Max.
Range
Parameter
Units Installation Setting
Modbus
Register
(dec)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CleaverBrooks CFC-1000 and is the answer not in the manual?

CleaverBrooks CFC-1000 Specifications

General IconGeneral
BrandCleaverBrooks
ModelCFC-1000
CategoryBoiler
LanguageEnglish

Related product manuals