InteliLite4 AMF20 Global Guide
196
Nominal Power – writing
Table: Setpoints
Allowed Modbus functions: 03, 04, 06, 16
Register
address
Com.Obj. Name Dimension Type Len Dec Min Max Group
03008 8276
Nominal
Power
kW Unsigned 2 0 1 5000
Basic
Settings
Request: (Numbers in Hex)
01 06 0B C0 00 64 8A 39
Controller address Modbus function
Register address
0BC0
hex
= 3008
dec
Data
0064
hex
=
100
dec
CRC
Response: (Numbers in Hex)
01 06 0B C0 00 00 8B D2
Controller address Modbus function
Register address
0BC0
hex
= 3008
dec
Allways zero CRC
Written setpoint nominal power is 100kW.
CRC calculation
The check field allows the receiver to check the validity of the message. The check field value is the Cyclical
Redundancy Check (CRC) based on the polynomial x
16
+x
15
+x
2
+1. CRC is counted from all message bytes
preceding the check field.
Online CRC calculator: http://www.lammertbies.nl/comm/info/crc-calculation.html Use CRC-16 (Modbus)
Write LSB first.
For writing nominal power 100kW the CRC is calculated from this data: 01060BC00064
hex

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals