Choke Time
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 .. 3600 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 13011 Related applications AMF,MRS
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 471) is configured and setpoint Choke Function
(page 229) = Fixed Time.
Description
Defines time logical binary output CHOKE (PAGE 471) is activated for when fixed time is used. When
setpoint Choke Function (page 229) is set to Temp Based value, Choke Time value have no effect.
Note: If setpoint Choke Lead (page 234) is set to nonzero value, total time the CHOKE output is
activated still matches value set by Choke Time setpoint. This mean Choke Timeshould be longer than
Choke Leadto ensure expected Choke behavior.
6 back to List of setpoints