InteliLite4 AMF20 Global Guide
234
Choke Lead
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 .. Prestart Time [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 15774 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 471) is configured.
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE (PAGE 471) is activated before logical
binary output STARTER (PAGE 501).
Note: In case Choke Lead is longer than 8s (cranking fail pause), Choke Lead will be limited to 8s
(cranking fail pause time). This limitation is applied only for cranking fail pause, Choke Lead in Prestart
stays unchanged.
6 back to List of setpoints