EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #233 background imageLoading...
Page #233 background image
InteliLite4 AMF20 Global Guide
233
Choke Voltage
Setpoint group Engine settings Related FW 1.3.0
Range [units] Disabled / 1–100 [%]
Default value Disabled Alternative config NO
Step 1 %
Comm object 15718 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 471) is configured.
Description
This setpoint adjust threshold level for deactivation of CHOKE (PAGE 471) binary output. When generator
voltage is higher than this level, then logical binary output CHOKE is deactivated. In multiphase system it is
sufficient to deactivate CHOKE LBO when at least one voltage crosses this threshold. In case setpoint
Choke Voltage is set to Disabled value, no voltage is taken into account and CHOKE LBO isn't deactivated
on the voltage basis.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals