InteliLite4 AMF20 Global Guide
232
Choke Increment
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0,00 .. 20,00 [s/°C]
Default value 0,00 s/°C Alternative config NO
Step 0,01 s/°C
Comm object 15715 Related applications AMF,MRS
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 471) is configured and setpoint Choke Function
(page 229) = Temp Based.
Description
This setpoint adjust the maximal time of activation of binary output CHOKE (PAGE 471). Calculated time
depends on engine (coolant) temperature. Setpoint adjust curve which is used for calculating actual
Choke Time. When setpoint Choke Function (page 229) is set to Fixed Time value, setpoint Choke
Increment has no effect.
Note: If setpoint Choke Lead (page 234) is set to nonzero value, total time the CHOKE output is
activated still matches calculated value (based on actual temperature and setpoints Choke Increment
and Choke Start Temp (page 231)) This mean that adjusted parameters should ensure that
calculated Choke Time will be longer than Choke Leadto ensure expected Choke behavior.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals