InteliLite4 AMF20 Global Guide
238
Maximal Stabilization Time
Setpoint group Engine settings Related FW 1.3.0
Range [units] Minimal Stabilization Time (page 237) .. 3600 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8313 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
When the Gen-set has been started and the idle timer has elapsed, the generator voltage and frequency
must get within limits within this period of time, otherwise an appropriate shutdown alarm (generator
voltage and/or frequency) is issued.
Note: When starting the engine, setpoint should be set >300s.
Image 8.6 Maximal Stabilization Time
6 back to List of setpoints