239
Run Only Block Delay
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0.0 .. 600.0 [s]
Default value 5.0 s Alternative config YES
Step 0.1 s
Comm object 10023 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
During the start of the Gen-set, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protect Hold Off. The time starts after reaching Starting RPM.
The protection blocking is based on the operating state of the engine automat. Once the engine automat
reaches the state "Running" the protection with this blocking condition gets unblocked after delay Run
Only Block Delay.
6 back to List of setpoints
Subgroup: Stopping
Cooling Speed
Setpoint group Engine settings Related FW 1.3.0
Range [units] Idle / Nominal [-]
Default value Nominal Alternative config NO
Step [-]
Comm object 10046 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
Selects the function of the binary output IDLE/NOMINAL (PAGE 487) during engine cooling state.
Idle Cooling is executed at Idle speed and generator protections are switched off.
Nominal Cooling is executed at Nominal speed and generator protections are active.
Note: When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note: Binary output IDLE/NOMINAL (PAGE 487) must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals