InteliLite4 AMF20 Global Guide
257
Maintenance Timer 1 Protection
Setpoint group Maintenance Timers Related FW 1.3.0
Range [units] Warning / BOC [-]
Default value Warning Alternative config NO
Step [-]
Comm object 20586 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Type of the maintenance alarm of both Maintenance Timer 1 RunHours (page 256) and Maintenance
Timer 1 Interval (page 256).
6 back to List of setpoints
Subgroup:Maintenance Timer 2
Maintenance Timer 2 RunHours
Setpoint group Maintenance Timers Related FW 1.3.0
Range [units] 0 ... 9 999 [h] / Disabled
Default value Disabled Alternative config NO
Step 1 h
Comm object 13854 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer counts down when engine is running. If it reaches zero, an alarm appears, but the timer
still counts down to negative values. When the value 10 000 (Disabled) is set, the Maintenance function is
disabled and the counter value disappears from controllers statistics.
Reset of the timer can be done by adjusting this setpoint again.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals