InteliLite4 AMF20 Global Guide
290
Time Stamp Period
Setpoint group Scheduler Related FW 1.3.0
Range [units] 0 .. 240 [min]
Default value 60 min Alternative config NO
Step 1 min
Comm object 8979 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Time interval for periodic history records.
Note: History record is made only when engine is running.
6 back to List of setpoints
DST Switching Mode
Setpoint group Scheduler Related FW 1.3.0
Range [units] - [AUTO / MANUAL / DISABLED]
Default value AUTO Alternative config NO
Step [-]
Comm object 20250 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Switches the mode of Daylight Saving Time (DST).
AUTO
Activation, deactivation of the DST, and changing of the RTC Time value
accordingly is performed automatically by the controller. The user always sees
valid local time without any action from his side.
MANUAL
Activation, and deactivation of the DST is performed manually by the user via the
setpoint Time Mode (page 291). Changing of the RTC Time value accordingly is
then performed automatically by the controller. So the user does not need to
readjust the RTC time, he only needs to select the proper Time Mode (page 291).
DISABLED
Time Mode (page 291) is fixedly set to STD and the function does not perform any
changes of RTC time.
6 back to List of setpoints