InteliLite4 AMF20 Global Guide
298
Timer 1 Refresh Period
Setpoint group Scheduler Related FW 1.3.0
Range [units] [-]
Default value [-] Alternative config NO
Step [-]
Comm object 0 Related applications AMF,MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Timer 1 Function (page 292)
Description
Refresh period of Timer 1 Function (page 292). Meaning of this setpoint depends on type of repetition
adjusted in Timer 1 Repeated (page 295).
Daily
Range [units]: 1 .. 1000 [day]. This setpoint adjust that every X day the timer
will be activated.
Example: If you have daily repetition and you set this setpoint to 2, then
every second day from first occurrence of Timer 1 Function (page 292),
the Timer 1 Function (page 292) will be activated.
Weekly
Range [units]: 1 .. 60 [week]. This setpoint adjust that every X week the timer
will be activated.
Example: If you have weekly repetition and you set this setpoint to 2, then
every second week from first occurrence of Timer 1 Function (page 292),
the Timer 1 Function (page 292) will be activated in selected days
adjusted by Timer 1 Day (page 296).
Monthly
Range [units]: 1 .. 12 [month]. This setpoint adjust that every X month the timer
will be activated.
Example: If you have monthly repetition and you set this setpoint to 2, then
every second month from first occurrence of Timer 1 Function (page 292),
the Timer 1 Function (page 292) will be activated in selected day of month
adjusted by Timer 1 Repeat Day In Month (page 296) or in selected days
of week of month adjusted by Timer 1 Day (page 296) and Timer 1
Repeat Week In Month (page 297).
Short Period
Range [units]: [HH:MM]. This setpoint adjust that every X short period the timer
will be activated.
Example: If you have short period repetition and you set this setpoint to 2,
then every second minute from first occurrence of Timer 1 Function (page
292), the Timer 1 Function (page 292) will be activated.
6 back to List of setpoints