EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #378 background imageLoading...
Page #378 background image
InteliLite4 AMF20 Global Guide
378
Nominal Frequency 2
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 30 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9914 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 439) is active.
6 back to List of setpoints
Nominal Voltage Ph-N 2
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 80 .. 20000 [V]
Default value 231 V Alternative config YES
Step 1 V
Comm object 12053 Related applications AMF,MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type 2 (page 379).
Description
Nominal system voltage (phase to neutral).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 439) is active.
6 back to List of setpoints
Nominal Voltage Ph-Ph 2
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 80 .. 40000 [V]
Default value 400 V Alternative config YES
Step 1 V
Comm object 12056 Related applications AMF,MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type 2 (page 379).
Description
Nominal system voltage (phase to phase).
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 439) is active.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals