InteliLite4 AMF20 Global Guide
384
Nominal Current 3
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1 A
Comm object 12051 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
It is current limit for generator current protections and means maximal continuous generator current.
Nominal Current can be different from generator rated current value.
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 439) is active.
6 back to List of setpoints
Connection type 3
Setpoint group Alternate Config Related FW 1.3.0
Range [units]
Mono Phase / SplPhL1L2 / SplPhL1L3 / 3Ph3Wire / 3Ph4Wire / High Leg D /
Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 12060 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Connection type:
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
SplPhL1L2 Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
SplPhL1L3 Double Delta connection
Split Phase
Two phase voltage measurement L1,L3 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals