InteliLite4 AMF20 Global Guide
486
LBO: H
Related FW 1.3.0 Related applications AMF,MRS
Comm object 81
Description
This output toggles on/off in a period of 500 ms whenever the controller is switched on and functional.
Heartbeat
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1
Description
The output designed to be used for acoustic indication of a newly appeared alarm. The output is activated
each time a new alarm has appeared and remains active until one of the following events occurs:
Fault reset is pressed
Horn reset is pressed
Horn Timeout (page 220) has elapsed
Horn
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 31
Description
This output provides 1s pulse when:
Horn Reset button is pressed on the controller front facia or
Horn Reset button is pressed on any of external local/remote terminals or
Horn Reset command is received via communication line or
the input HORN RESET BUTTON is activated.
HornRes Button Echo
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 2696
Description
LBO is active as long as it's button is pressed or it's LBI is active.
HornRes Button State
6 back to Logical binary outputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals