InteliLite4 AMF20 Global Guide
544
Alarm evaluated Wrn Battery > Voltage
Related applications AMF,MRS
Description
This alarm informs the operator that the controller supply voltage is too high. The
following setpoints are related to it:
Battery Overvoltage (page 253)
Battery <> Voltage Delay (page 253)
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Wrn Battery < Voltage
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm informs the operator that the controller supply voltage is too low. The
following setpoints are related to it:
Battery Undervoltage (page 252)
Battery <> Voltage Delay (page 253)
Wrn Battery Undervoltage
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Wrn Password reset e-mail addr is not set
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm is active when there is no email address set in the controller and
simultaneously controller administrator password is not the default password.
Note: When default password is changed the Wrn Password reset e-mail
addr is not set will be active after the restart of the controller.
Wrn Password reset e-mail addr is not set
6 back to List of alarms level 1
Alarm Type ALI
Alarmlist message Manual Restore
Alarm evaluated All the time
Related applications AMF,MRS
Description
Alarm is activated when controller is in AUTO mode, Return From Island (page
281) setpoint is set to manual, load is on Gen-set and mains has returned.
Manual Restore
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Override All Sd
Wrn Override All Sd