InteliLite4 AMF20 Global Guide
604
CAN address
Controller type selection
The type of controller to be used with IGS-PTM must be selected via jumper labelled IGS accessible at the
lower PCB.
IGS jumper Controller type
OPEN IL-NT, IC-NT
CLOSE IG-NT, IS-NT, InteliLite
Address configuration
If InteliLite controller type is selected (by IGS jumper), address of IGS-PTM could be modified via jumpers
labelled ADR1 and ADR2.
ADR1 ADR2 ADR offset BIN module
BOUT
module
AIN module
Open Open 0 (default) 1 1 1
Close Open 1 2 2 2
Open Close 2 3 3 3
Close Close 3 4 4 4
Programming firmware
Firmware upgrade is available via AT-link (TTL). For programming it is necessary to close jumper BOOT.
RESET jumper is used to reset the device. Close jumper to reset the device. For programming FlashProg PC
tool should be used.
LED indication
Binary input
Each binary input has an LED which indicates input signal. LED is shining when input signal is set, and LED is
dark while input signal has other state.
Binary output
Each binary output has an LED which indicates output signal. Binary output LED is shining when binary
output is set.
LEDat power connector – status LED
LEDstatus Description
Dark No required power connected.
Quick flashing Program check failure.
One flash and pause Compensation fail.
Three flashes and
pause
Compensation successful.
Flashes There is no communication between IGS-PTM and the controller.
Lights
Power supply is in the range and communication between IGS-PTM and
controller properly works.