Fast flashing Detection of CAN communication speed
Lights
Power supply is in the range and the communication between Inteli AIN8TC and
controller works properly.
Or power supply is in range and zero CAN address is set. (in case zero CAN
address module doesn’t communicate with the controller)
Wiring
The following diagrams show the correct connection of sensors.
Measuring resistance AIN9
2 wire measurement
Ranges: Pt1000, Ni1000, 0 2400 Ω.
Analog input 9 is determined for measuring resistance only.
Technical data
Dimension (W × H × D) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 248 grams
Interface to controller
CAN1 galvanic separated from power supply