EasyManua.ls Logo

ComAp InteliLite 4 AMF 20

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite4 AMF20 Global Guide
615
Fast flashing Detection of CAN communication speed
Lights
Power supply is in the range and the communication between Inteli AIN8TC and
controller works properly.
Or power supply is in range and zero CAN address is set. (in case zero CAN
address module doesn’t communicate with the controller)
Wiring
The following diagrams show the correct connection of sensors.
Measuring resistance AIN9
2 wire measurement
Ranges: Pt1000, Ni1000, 0 2400 Ω.
Analog input 9 is determined for measuring resistance only.
Technical data
Dimension (W × H × D) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 248 grams
Interface to controller
CAN1 galvanic separated from power supply
and measurement,

Table of Contents

Related product manuals