InteliLite4 AMF20 Global Guide
614
Analog outputs
1 channel AOUT1. Type of output:
0-10V DC
0-20mA
PWM (5V, freq 2.4Hz ÷2.4kHz)
Analog output has 4-pins connector GND and one pin for each type of output.
All analog inputs can be configured to any logical function or protection.
Supported sensors
Sensors
User curves
PT1000 [°C] (fix)
NI1000 [°C] (fix)
PT1000 [°F] (fix)
NI1000 [°F] (fix)
0-2400 (fix linear)
±65 V DC (fix linear)
±75mV (fix linear)
Thermocpl J [°C] (fix)
Thermocpl K [°C] (fix)
Thermocpl L [°C] (fix)
Thermocpl (nc) J [°C] (fix)
Thermocpl (nc) K [°C] (fix)
Thermocpl (nc) L [°C] (fix)
Thermocpl (nc) J [°F] (fix)
Thermocpl (nc) K [°F] (fix)
Thermocpl (nc) L [°F] (fix)
Address and DIP switch setting
Address configuration
DIP switch determinates CAN address for analog inputs and outputs.
Programming Firmware
Firmware upgrade is available via AT-link (TTL). For programming it is necessary to close jumper TEST and
switch OFF and ON the power supply.
For programming use FlashProg PC tool version 4.4 or higher.
LED indication
LED status Description
Dark Fw in module does not work correctly.
Flashing Module does not communicate with controller (in case non-zero CAN address)