Subgroup: Controller settings
Setpoint group Basic settings Related FW 1.9.0
Range [units] OFF / MAN / AUTO[-]
Default value OFF Alternative config NO
Step [-]
Comm object 8315 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via MODBUS. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from InteliConfig.
Controller mode
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] Previous / OFF [-]
Default value Previous Alternative config NO
Step [-]
Comm object 13000 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts controller mode after power on of controller.
Previous When controller is power on, than is switched into last mode before power off.
OFF When controller is power on, than is switched into OFF mode.
Note: Remote modes - In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint - controller mode is forced into mode selected via LBI.
After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode
Power On Mode
6 back to List of setpoints