InteliLite Global Guide
356
Setpoint group Basic settings Related FW 1.9.0
Range [units] 80 .. 20000 [V]
Default value 231 V Alternative config YES
Step 1 V
Comm object 12052 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection Type 1 (page 353).
Description
Nominal system voltage (phase to neutral).
Note: This value is used when any other alternate configuration is not active.
Nominal Voltage Ph-N 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.9.0
Range [units] 80 .. 40000 [V]
Default value 400 V Alternative config YES
Step 1 V
Comm object 12055 Related applications AMF, MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection Type 1 (page 353).
Description
Nominal system voltage (phase to phase).
Note: This value is used when any other alternate configuration is not active.
Nominal Voltage Ph-Ph 1
6 back to List of setpoints