EasyManuals Logo

ComAp InteliLite AMF25 User Manual

ComAp InteliLite AMF25
735 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #358 background imageLoading...
Page #358 background image
InteliLite Global Guide
358
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW 1.9.0
Range [units] [-]
Default value airgate.comap.cz Alternative config NO
Step [-]
Comm object 24364 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint Internet Connection
(page 359) (CM-GPRS module)
Description
This setpoint is used for entering the domain name or IP address of the AirGate server. Use the free AirGate
server provided by ComAp at airgate.comap.cz.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
AirGate Address
6 back to List of setpoints
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW 1.9.0
Range [units] 0 .. 65 535[-]
Default value 23 Alternative config NO
Step [-]
Comm object 24374 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint Internet Connection
(page 359) (CM-GPRS module)
Description
This setpoint is used to adjust the port number, which is used for Ethernet connection to a PC with any of
ComAp PC program (i.e. InteliConfig). This setpoint should be adjusted to 23, which is the default port used
by all ComAp PC programs. A different value should be used only in special situations as e.g. sharing one
public IP address among many controllers or to overcome a firewall restrictions.
IMPORTANT: If AirGate is used, this setpoint has to be adjusted to 23.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
ComAp TCP Port
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals