InteliLite Global Guide
371
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW 1.9.0
Range [units] 0 .. 65 535[-]
Default value 23 Alternative config NO
Step [-]
Comm object 24374 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint Internet Connection
(page 359) (CM-GPRS module)
Description
This setpoint is used to adjust the port number, which is used for Ethernet connection to a PC with any of
ComAp PC program (i.e. InteliConfig). This setpoint should be adjusted to 23, which is the default port used
by all ComAp PC programs. A different value should be used only in special situations as e.g. sharing one
public IP address among many controllers or to overcome a firewall restrictions.
IMPORTANT: If AirGate is used, this setpoint has to be adjusted to 23.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
ComAp TCP Port
6 back to List of setpoints
Group: CM-Ethernet
Setpoint group
CM-GPRS; CM-4G-
GPS; CM-Ethernet
Related FW 1.9.0
Range [units] 0..63 characters [-]
Default value [-] Alternative config NO
Step [-]
Comm object 24298 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint Internet Connection
(page 359) (CM-GPRS and CM-4G-GPS modules)
Description
Enter in this setpoint a valid e-mail address where the alarm and event e-mails shall be sent. Leave this
setpoint blank if alarm and event email should not be send.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Email Address 1
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals