InteliLite Global Guide
385
Setpoint group CM-Ethernet Related FW 1.9.0
Range [units] Disabled / Enabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 24110 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint IP Address Mode
(page 378)
Description
The setpoint is used to enable/disable WebServer function.
Web Interface
6 back to List of setpoints
Group: EM-BIO8-EFCP
Setpoint group EM-BIO8-EFCP Related FW 1.9.0
Range [units] DISABLED / ENABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 11631 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
This setpoint can block or allow Earth fault Current protection.
DISABLED Earth fault current protection is blocked.
ENABLED Earth fault current protection is allowed. Behavior of Earth fault current protection is set
by these setpoints: Earth Fault CT Input Range (page 386), Earth Fault CT Ratio
(page 386), Earth Fault Delay (page 386) and Earth Fault Sd (page 387).
Earth Fault Current Protection
6 back to List of setpoints