InteliLite Global Guide
655
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message All the time
Alarm evaluated Wrn Battery > Voltage
Related applications AMF, MRS
Description
This alarm informs the operator that the controller supply voltage is too high. The
following setpoints are related to it:
Battery Overvoltage (page 221)
Battery <> Voltage Delay (page 221)
Wrn Battery > Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Battery < Voltage
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm informs the operator that the controller supply voltage is too low. The
following setpoints are related to it:
Battery Undervoltage (page 220)
Battery <> Voltage Delay (page 221)
Wrn Battery < Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn + Name of binary input
Alarm evaluated All the time
Related applications AMF, MRS
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - Wrn and binary input name. This alarm occurs, when appropriate
binary input is active.
Wrn BIN Protection
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Charging Alternator Fail
Alarm evaluated Engine running only
Related applications AMF, MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than D+ Treshold (page 206) of the controller supply voltage. This alarm
works similar to the red “battery” alarm indicator on a vehicle dashboard.
The setpoint has to be in Charge Fail or Enabled position to enable this alarm.
Wrn Charging Alternator Fail