InteliLite Global Guide
665
Alarm Type Alarm indication
Alarmlist message Dual Operation Fail
Alarm evaluated Only during dual operation
Related applications AMF, MRS
Description
This alarm is active when there is fail between controllers in dual operation
function.
Exapmles:
No connection - disconnection of cable
No connection - incorrect settings of COM Modes
Controllers not in AUTO mode
Different Operation Modes (AMF controllers only)
Different FW versions in controllers
Different mains statuses in controllers (AMF controllers only)
Note: This alarm is also written to history.
Dual Operation Fail
6 back to List of alarms level 1
Alarm Type Alarm indication
Alarmlist message Dual Operation Master Fail
Alarm evaluated Only during dual operation
Related applications AMF, MRS
Description
This alarm is active when Master is not able to take the load e.g. there is alarm of
2nd level on Master. Logical binary input AL DUAL MASTER FAIL (PAGE 546) is
activated.
Note: This alarm is also written to history.
Dual Operation Master Fail
6 back to List of alarms level 1
Alarm Type Alarm indication
Alarmlist message Dual Operation Slave Fail
Alarm evaluated Only during dual operation
Related applications AMF, MRS
Description
This alarm is active when Slave is not able to take the load e.g. there is alarm of
2nd level on Slave. Logical binary input AL DUAL SLAVE FAIL (PAGE 546) is
activated.
Note: This alarm is also written to history.
Dual Operation Slave Fail
6 back to List of alarms level 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals