Alarm Type Warning
Alarmlist message ECU Wait To Start
Alarm evaluated Only when ECU is connected
Related applications AMF, MRS
Description
This alarm is activated when ECU send information that ECU Wait To Start lamp
is activated. LBO ALARM (PAGE 552)is not activated, after deactivation of lamp,
alarm automatically disappear.
ECU Wait To Start
6 back to List of alarms level 1
Alarm Type Alarm indication + history record
Alarmlist message ECU Yellow Lamp
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm is activated when ECU send information that ECU Yellow lamp is
activated. LBO ALARM (PAGE 552)is not activated, after deactivation of lamp,
alarm automatically disappear.
ECU Yellow Lamp
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - a message lost
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
EM(A) - a message lost
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - configuration mistake
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with configuration of binary input or
output of module in slot.
EM(A) - configuration mistake