IGS-NT Installation Guide
120
Heinzmann
Sync/Load ctrl:
Speed gov bias = 0,00 V
SpeedRegChar =
POSITIVE
Sync/Load ctrl:
Speed gov bias = 5,00 V
SpeedRegChar =
POSITIVE
A3
B3
Heinzmann
E16
SG COM
SG OUT
VoutR
Sync/Load ctrl:
Speed gov bias = 0,00 V
SpeedRegChar =
POSITIVE
7
Heinzmann
SG COM
SG OUT
VoutR
PANDAROS
DC6
8
10kohm
Terminals A3 and B3 are on OEM 14-pin connector.
Mounted on Perkins 40xx engines.
Sync/Load ctrl:
Speed gov bias = 5V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0,8V
For connection w/o resistor
refer to the next setting
2
Heinzmann
SG COM
SG OUT
VoutR
PANDAROS
DC6
1
Sync/Load ctrl:
Speed gov bias = 2,7V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0V
SpeedGovHighLim = 6V
ComAp
7
SG COM
SG OUT
Vout
ECON 4
8
Sync/Load ctrl:
Speed gov bias = 5,1V
SpeedRegChar =
POSITIVE
SpeedGovLowLim = 0,0V
SpeedGovHiLim = 10V
Caterpillar PEEC
SG COM
SG OUT
PWM
19
C
aterpillar
PEEC
9
Sync/Load ctrl:
SpdGovPWM rate = 500
Hz

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals